Search FAQs
How to enable Simple Network Management Protocol (SNMP) on ASCO Quad-Ethernet Module (QEM) – 5140 and 5170?
Simple Network Management Protocol (SNMP) on ASCO Quad-Ethernet Module (QEM)
To enable SNMP functionality in the QEM, go to the Ethernet Module Configuration Screen in Edit Mode and select the SNMP tab.
Notes:
You can configure a maximum of three (3) SNMP managers. All the managers must have the same settings for GET & TRAP ports; as well as with their GET & TRAP community names.
Configuring the SNMP master to view traps is master systems dependent and needs the following information:
• The IP address of the QEM
• The MIB file: ASCO-QEM-987302-xxx.mib (on website)
With regards to SNMP traps, the QEM sends traps from the list of alerts that it monitors which are listed in the Email Alert Notification and SNMP Traps configuration window. Note that these alerts are also used to initiate email alerts if SMTP is enabled.
The QEM and the SNMP master(s) should be on the same network.
Details of configuring the SNMP master to view traps are master dependent.
Reference and Links:
To enable SNMP functionality in the QEM, go to the Ethernet Module Configuration Screen in Edit Mode and select the SNMP tab.
- The ASCO QEM acts as a SNMP agent, providing data to a SNMP Manager on demand. The QEM supports the GET, GETNEXT, GETBULK, TRAP, and RESPONSE commands (SNMP v1 and v2)
- The QEM does not support the SET or INFORM commands and it does not support SNMP v3
Notes:
You can configure a maximum of three (3) SNMP managers. All the managers must have the same settings for GET & TRAP ports; as well as with their GET & TRAP community names.
Configuring the SNMP master to view traps is master systems dependent and needs the following information:
• The IP address of the QEM
• The MIB file: ASCO-QEM-987302-xxx.mib (on website)
With regards to SNMP traps, the QEM sends traps from the list of alerts that it monitors which are listed in the Email Alert Notification and SNMP Traps configuration window. Note that these alerts are also used to initiate email alerts if SMTP is enabled.
The QEM and the SNMP master(s) should be on the same network.
Details of configuring the SNMP master to view traps are master dependent.
Reference and Links:
- https://download.schneider-electric.com/files?p_enDocType=User+guide&p_File_Name=381333-459C.pdf&p_Doc_Ref=PCM-UM-51405170QEM
- https://www.ascopower.com/us/en/download/document/PCM-SOF-QEM987302-001/
- https://www.ascopower.com/us/en/product-range/66136-asco-5140-quad-ethernet-module/?parent-subcategory-id=88402367#software-and-firmware
Published for:ASCO Power Technologies USA
Explore more
Range:
Explore more
Range: