Our Brands

My Documents 0

Welcome to the ASCO Website

Welcome to our website.
        

Search FAQs

How to connect Accessory 1UP with Group G controller?

There is an accessory kit available for accessory 1UP.
Part Number: 935149

The accessory 1UP kit includes these items:
  • 1UP module
  • DIN rail
  • shake-proof hex nuts (for mounting the DIN rail)
  • ribbon cable (to controller or another accessory)
image.png

Installation Procedure:
1. Deenergize the transfer switch. Then open the enclosure door and verify that all power is off.
2. Mount the DIN rail onto two short studs (on the door) below the controller. If a DIN rail is already installed it may have room for the 1UP module. See Figures 1 and 2. It may be easier to install the 1UP module onto the DIN rail before mounting the DIN rail.

image.png
3. Install the 1UP module onto the DIN rail (right side). Hook the top of the module onto the DIN rail and rock it downward until it snaps in place.
4. Connect the ribbon cable between 1UP module (J3) and controller (J3). If Acc. 18RX relay expansion
module(s) is already installed, connect 1UP (J3) to the Acc. 18RX module that has an unconnected (J12A). The 1UP module must be the last item in the chain.

Refer to the following links for more information:
  • Group G User’s Manual: https://www.ascopower.com/us/en/download/document/ASC-TS-UM-300G-CONTROL/
  • 1UP Installation Manual: https://www.ascopower.com/us/en/download/document/TS-UM-300ACCESS1UP/