Search FAQs
How to simulate a wiring fault to test if the ASCO 5101 is working?
After the 5101 has been configured and set accordingly based on the customer’s application,
simulate a wiring fault by:
1.) Removing the channel input terminal block on the front of the 5101- Generator module

2. Verify the channel Led indication should change to “RED”

3. The alarm relay should de-energize; If the channel terminal block is reconnected to the Generator module, the channel Led indication should return to “Green” and relay should be energized. Refer to (5101) Engine Start Monitoring system Installation Manual (381333-474 F) for further reference. Please click HERE .



If unsure, please contact Technical Support @ 1-800-800-2726 and press 3 or send an email to technicalsupport@ascopower.com
simulate a wiring fault by:
1.) Removing the channel input terminal block on the front of the 5101- Generator module
2. Verify the channel Led indication should change to “RED”
3. The alarm relay should de-energize; If the channel terminal block is reconnected to the Generator module, the channel Led indication should return to “Green” and relay should be energized. Refer to (5101) Engine Start Monitoring system Installation Manual (381333-474 F) for further reference. Please click HERE .
If unsure, please contact Technical Support @ 1-800-800-2726 and press 3 or send an email to technicalsupport@ascopower.com
Published for:ASCO Power Technologies USA
Attachment(s)
Did this answer your question?
Explore more
Explore more