Our Brands

My Documents 0

Welcome to the ASCO Website

Welcome to our website.

Basic Power Source Synchronization and Paralleling

Power source synchronization and power source paralleling are topics that must be understood to properly design backup power systems. Synchronization focuses on the relative difference in frequency between connectable circuits and, together with voltage differences, must be considered when transferring loads between power sources. For source paralleling applications, where two power sources must feed the same load, solutions must also account for phase angle differences.

Synchronizing Power Sources for Load Transfer

The frequency of alternating current is a function of generator speed, which varies with the speed of the prime mover. When comparing the frequencies of two power sources, such as during retransfer from backup power to utility power, the power sources must exhibit an acceptable frequency difference, typically less than 0.2 cycles per second (Hertz). This is necessary to ensure a successful transfer with minimal transient electrical or mechanical effects.

Graph for Power Sources for Load Transfer
Figure 1: Synchronization typically requires a frequency difference of less than 0.2 Hertz.
Connection of two power sources may be problematic if only frequency differences are considered. Because current will flow from high potential to low potential, line voltage differences must also be limited to avoid large inrush currents or reverse power flow. For these reasons, voltage differences must be within an acceptable range, typically +/-5 percent.

Graph for Power Source Synchronization and Paralleling
Figure 2: Synchronization typically requires a voltage difference of less than five percent.
The Role of Phase Angle Differences

As noted, current will always flow from locations of high potential to low potential. In addition to the line voltages of two sources, voltage differences also result from the instantaneous difference in phase angles that result from any difference in rotational positions of generators and/or motors at the instance of connection. Upon connection, phase angle differences may produce current that attempts to force motors and/or generators to rotate in unity. Phase angles differences and the resulting sine waves are illustrated in the following figure.

Graph for Power Source Synchronization and Paralleling
Figure 3: A difference in phase angle of motors and/or power sources at t0 results in an instantaneous voltage difference
Connecting power sources when phase angle differences are large can result in strong inrush currents. When inductive loads are present, these currents electrically and mechanically stress equipment and can lead to:
  • electrical damage to electrical and electronic components
  • mechanical damages to rotating mechanical equipment such as engines, generators, electric motors, and the equipment they power
  • nuisance tripping of overcurrent protection devices
For these reasons, phase angle differences must be managed when closing alternate power sources.

Approaches for Managing Phase Angle Differences

When transferring mixed or resistive loads using an open transition transfer switch, phase angle differences may not require further consideration. However, phase angle differences must be managed when significant inductive or motor loads are present. Two approaches are available.

For transfer switching, In-Phase Monitoring can be used to ensure that connection occurs only when phase angle differences are within acceptable ranges. With in-phase monitoring, transfer switch controllers passively allow power sources to drift towards synchronicity, then initiate transfer so that connection completes when phase angle differences are acceptable. For most load transfer applications, the maximum acceptable difference is 60 degrees.

Source paralleling is conducted by switchgear, and typically involves larger amounts of power. Like in-phase monitoring, switchgear must account for phase angle differences when connecting power sources such as two large generators with high inertial loads. Here, phase angle differences must be more tightly controlled, typically within 5 degrees.

Unlike in-phase monitoring, paralleling solutions actively manipulate engine controls. These may be used to drive power sources to synchronicity and to reduce phase angle differences, and are needed to maintain synchronization until each genset is no longer required

Summary

Synchronization focuses on the relative difference in frequency between connectable equipment, and is necessary when transferring loads between power sources. Transfer switches can assure reliable load transfer without excessive transient effects by connecting to alternate power sources only when frequency and voltage differences are acceptable. Where inductive or motor loads are present, in-phase monitoring can be used to close on power sources as they drift into synchronicity. For transfer switching operations, acceptable voltage, frequency, and phase angle differences are typically +/- 5 percent, +/- 0.2 Hertz, and +/- 60 degrees, respectively.

Source paralleling involves larger amounts of power. It requires control of the same parameters as synchronization plus control of phase angle differences. Source paralleling solutions actively adjust engine controls to establish and maintain synchronism and control phase angle differences. For connection, acceptable voltage, frequency, and phase angle differences are typically +/- 5 percent, +/- 0.2 Hertz, and +/- 5 degrees, respectively. Paralleling solutions synchronize power sources until multiple sources are no longer needed.

Get the latest white papers, product news and insights straight to your inbox

Subscribe Now